Procedure for resetting the default CMOS setting.
The following procedure is for CP-100 consoles that have had their CMOS default settings altered.
This error can occur as a result of static shock or heavy electrical fluctuation in various environments.
The solution is possible to do without a monitor connected. However it is a darn sight easier if you
can connect one up. If you want to connect up a monitor you are going to have to have fitted a video
card. Video cards are available from your Elektralite distributor or from Elektralite direct.
SYMPTOM
: The Disk Drive appears not to work.
SOLUTION
: Perform the following steps.
1-
Connect a standard Windows 95 keyboard to the keyboard jack on the rear panel of the console.
2-
Power up the console.
3-
Hold the “Del.” button on the keyboard for 15 seconds.
4-
Press “Enter”
5-
Press the down arrow key 8 times.
6-
Press the “Page Up” key 2 times.
7-
Press “Esc.”
8-
Press the down arrow key 3 times.
9-
Press “Enter”
10-
Press “y”
11-
Press “Enter”
12-
Press “F10”
13-
Press “y”
14-
Press “Enter”
15-
Wait for complete reboot of the software (approximately 30 seconds)
This restores the default settings of the operating system and reconfigures it to recognize the diskette
drive.